Netsure 531 A31
Especificações
Technical Specifications
Netsure 531 A31
- Product Overview
- Power Capacity
- 2 kW - 6 kW
- Current Capacity
- 42 A - 125 A
- System Type
- Subrack
- Input
- Input Voltage, Nominal
- 200 VAC - 250 VAC
- Input Voltage, Operational
- 85 VAC - 300 VAC
- Equipment Dimensions (H x W x D)
- Subrack: 132 mm x 483 mm x 310 mm, Rectifier: 41 mm x 84.5 mm x 252.5 mm
- Access
- Front Access
- Output
- Output Voltage, Nominal
- 48 VDC
- Output Voltage, Operational
- -42 VDC to -58 VDC
- Output Capacity
- Rectifier: 2000 W (max up to 3 units)
- Peak Efficiency
- Rectifier: 96.2%
- Load Circuit Breakers / Fuses
- Circuit Breakers
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- Circuit Breakers
- Peso (lbs / kgs)
- Subrack: ≤16 kg, Rectifier: 1.13 kg
- Altura (pol/mm)
- 132 mm
- Largura (pol/mm)
- 483 mm
- Profundidade (pol/mm)
- 310 mm
- Environmetal & Standard Compliance
- Control and Monitoring
- NCU controller with remote access via web browsers, TCP/IP & SNMP as standard
- Temperatura de Operação
- -40 to 80°C, Derating from 65°C
- Safety Compliance
- UL 60950-1, EN 60950-1, IEC 60950
- EMC Compliance
- ETSIEN300386,Class B; FCC CFR47 Part 15, Class B; EN55022, Class B. CISPR22, Class B; Telcordia GR-1089-CORE issue 6.