Quick Access
NetSure 512 582137000 up to 100A
Quick Access
Specifications
Technical Specifications
NetSure 512 582137000 up to 100A
- Product Overview
- Power Capacity
- 2-4.8kW / 1.5kW
- Current Capacity
- 40-100A / 50A
- System Type
- Single row system
- Input
- Input Voltage, Nominal
- Single phase: 208VAC to 240VAC
- Input Voltage, Operational
- Rectifier: (Single Phase) 85 VAC to 300 VAC, DC-DC Converter: 41 VDC to 58.5 VDC
- Input Connections
- Molex for AC cords or hardwiring
- Equipment Dimensions (H x W x D)
- Distribution cabinet: 4U x 23" x 14.25", Module shelf: 1U x 23" x 15"
- Access
- Top or rear cabled with front and top access
- Output
- Output Voltage, Nominal
- -48VDC, +24VDC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC, -48V to +24V Converter: +24 VDC to +28 VDC
- Output Capacity
- Up to 100 amps at -48 VDC plus redundancy, Up to 50 amps at +24 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96.2%, -48V to +24V Converter: 95%
- Load Circuit Breakers / Fuses
- 1-250 A E/M or E bullet nose breakers, 3-100 A TPS/TLS fuses, 18/100 A to 15 A GMT fuses
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- 1A to 250 A E/M or E breakers, Fuses 3 A to 100 A TPL/TLS
- Options
- SM-Temp
- Environmetal & Standard Compliance
- Control and Monitoring
- NCU with remote access via web browsers, TCP/IP & SNMP as standard
- Operating Temperature
- -40 °C to +65 °C ( 40 °F to +149 °F)
- Safety Compliance
- UL Recognized (cUL)
*To see model-specific downloads, you will need to go to the model-specific product page by selecting the model name in the specifications chart above.