Quick Access
NetSure 512 582137000 up to 525A
Quick Access
Specifications
Technical Specifications
NetSure 512 582137000 up to 525A
- Product Overview
- Power Capacity
- 18-28.8kW / 1.5-19.2kW
- Current Capacity
- 40-600A / 50-400A
- System Type
- Two row system
- Input
- Input Voltage, Nominal
- Single phase: 208VAC to 240VAC
- Input Voltage, Operational
- Rectifier: (Single Phase) 85 VAC to 300 VAC, DC-DC Converter: 41 VDC to 58.5 VDC
- Input Connections
- Molex for AC cords or hardwiring
- Equipment Dimensions (H x W x D)
- Distribution cabinet: 8U x 27" x 16", Module shelf: 1U x (19" or 23") x 15"
- Access
- Top or rear cabled with front and top access
- Output
- Output Voltage, Nominal
- -48 VDC, +24 VDC, -58 VDC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC; Converter: +24 VDC to +28 VDC or -56 VDC to -58 VDC
- Output Capacity
- Up to 600 amps at -48 VDC plus redundancy; Up to 400 amps at +24 VDC or -58 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96.2%; Converter: 95% (+24 VDC or -58 VDC)
- Load Circuit Breakers / Fuses
- 1-250 A E/M or E bullet nose breakers, 3-100 A TPS/TLS fuses, 18/100 A to 15 A GMT fuses
- Physical Characteristics
- Options
- SM-Temp
- Environmetal & Standard Compliance
- Control and Monitoring
- NCU with remote access via web browsers, TCP/IP & SNMP as standard
- Operating Temperature
- -40 °C to +65 °C ( 40 °F to +149 °F)
- Safety Compliance
- UL Recognized (cUL)
- IM582137000 NetSure 512 Installation Manual
- UM582137000, Model 512 NGBB User Manual
- UM1R482000E3 eSure Rectifier User Manual
- UM1C48241500 Converter User Manual
- UM547490 SM-TEMP User Manual
- QS582137000 Quick Start Guide Manual
- UM1R483500E Rectifier User Manual
- UM1C48582000P3 eSure Power Extend Converter User Manual